u
o3: Copy Function
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o3-01
(515)
Copy Function Selection
COPY SELECT
0: COPY SELECT
1: INV→OP READ
2: OP→INV WRITE
3: OP←→INV
VERIFY
0: No action
1: Read parameters from the drive, saving them onto the HOA
keypad.
2: Copy parameters from the HOA keypad, writing them to the
drive.
3: Verify parameter settings on the drive to check if they match
the data saved on the HOA keypad.
Default: 0
Range: 0 to 3
o3-02
(516)
Copy Allowed Selection
Read Allowable
0: Disabled
1: Enabled
0: Read operation prohibited
1: Read operation allowed
Default: 0
Range: 0, 1
u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o4-01
(50B)
Cumulative Operation
Time Setting
DrvElapsTimeCnt
Sets the value for the cumulative operation time of the drive in
units of 10 h.
Default: 0 h
Min.: 0
Max.: 9999
o4-02
(50C)
Cumulative Operation
Time Selection
ElapsTimeCntSet
0: Power-On Time
1: Running Time
0: Logs power-on time
1: Logs operation time when the drive output is active (output
operation time).
Default: 1
Range: 0, 1
o4-03
(50E)
Cooling Fan Operation
Time Setting
FanElapsTimeCn
Sets the value of the fan operation time monitor U4-03 in units
of 10 h.
Default: 0 h
Min.: 0
Max.: 9999
o4-05
(51D)
Capacitor Maintenance
Setting
BusCap Maint Set
Sets the value of the Maintenance Monitor for the capacitors. See
U4-05 to check when the capacitors may need to be replaced.
Default: 0%
Min.: 0
Max.: 150
o4-07
(523)
DC Bus Pre-Charge
Relay Maintenance
Setting
ChrgCircMaintSet
Sets the value of the Maintenance Monitor for the soft charge
bypass relay. See U4-06 to check when the bypass relay may need
to be replaced.
Default: 0%
Min.: 0
Max.: 150
o4-11
(510)
U2, U3 Initialization
Fault Data Init
0: No Reset
1: Reset
0: U2-
oo
and U3-
oo
monitor data is not reset when the drive
is initialized (A1-03).
1: U2-
oo
and U3-
oo
monitor data is reset when the drive is
initialized (A1-03).
Default: 0
Range: 0, 1
o4-12
(512)
kWh Monitor
Initialization
kWh Monitor Init
0: No Reset
1: Reset
0: U4-10 and U4-11 monitor data is not reset when the drive is
initialized (A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is
initialized (A1-03).
Default: 0
Range: 0, 1
o4-13
(528)
Number of Run
Commands Counter
Initialization
Run Counter Init
0: No Reset
1: Reset
0: Number of Run commands counter is not reset when the drive
is initialized (A1-03).
1: Number of Run commands counter is reset when the drive is
initialized (A1-03).
Default: 0
Range: 0, 1
o4-17
(3100)
Set/Reset Real Time
Clock
Set Time
0: — —
1: Set
2: Reset
Sets the current date and time for the Real Time Clock.
0: — — No Setting
1: Real Time Clock Set
2: Real Time Clock Reset
Default: 0
Range: 0 to 2
A.12 o: Operator-Related Settings
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
223
A
Parameter List