1.4 d: Reference Settings
The figure below gives an overview of the reference input, selections, and priorities.
=4
=0
=1
=2
=3
b1-01
(Freq.Reference Source1)
S5-05
d1-16
Terminal A1/A2
b1-01
(Freq.Reference Source1)
S5-01
(HAND Fref Source)
Terminal A1/A2
MEMOBUS/Modbus
Comm.
Option Card
d1-01
(Freq.Ref.1)
=3
=2
=1
=0
b1-01
(Freq.Reference Source1)
d1-17
d1-17
HOA Keypad (d1-01)
HOA Keypad (d1-04)
HOA Keypad (d1-03)
HOA Keypad (d1-02)
Terminal A1/A2
MEMOBUS/Modbus Comm.
Option Card
=0
=1
=2
=6
Frequency Reference
Terminal A1/A2
MEMOBUS/Modbus
Comm.
Option Card
d1-01
(Freq.Ref.1)
=3
=2
=1
=0
AUTO,OFF
HAND
d2-03
(Freq.Ref.Lower Limit)
Multi-Step Speed
Set by b1-01
0
0
1 1
NetRef
ComRef
d2-03
(Freq.Ref.Lower Limit)
Multi-Step Speed
S5-01<4
& HAND
JOG
EmergencyOverride
: OFF
=3
=4
=5
Sequence Timer Operation Enable
OFF when using
Option Card
Figure 1.23 Frequency Reference Setting Hierarchy
u
d1: Frequency Reference
n
d1-01 to d1-04, d1-16, and d1-17: Frequency References 1 to 4, HAND Frequency Reference 1,
and Jog Frequency Reference
The drive lets the user switch between up to 5 preset frequency references during run (including the Jog reference) through
the digital input terminals. The drive uses the acceleration and deceleration times that have been selected when switching
between each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate digital input.
The multi-speed references 1 and 2 can be provided by analog inputs.
No.
Parameter Name
Setting Range
Default
d1-01 to d1-04
Frequency Reference 1 to 4
0.00 to 240.00 Hz
d1-16
HAND Frequency Reference 1
0.00 to 240.00 Hz
d1-17
Jog Frequency Reference
0.00 to 240.00 Hz
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is “Hz” (o1-03 = 0).
Multi-Step Speed Selection
To use several speed references for a multi-step speed sequence, set the H1-
oo
parameters to 3 and 4. To assign the Jog
reference to a digital input, set H1-
oo
to 6.
Notes on using analog inputs as Multi-Speed 1 and 2:
• The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input terminal
to supply the frequency reference, assign the frequency reference source to the control terminals (b1-01 = 1).
• When an analog input is set to “Auxiliary frequency 1” (H3-02 or H2-06 = 2), the value set to this input will be used as the
Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for “Auxiliary frequency 1”, then
d1-02 becomes the reference for Multi-Step Speed 2.
Select the different speed references as shown in
.
illustrates the multi-step speed selection.
1.4 d: Reference Settings
56
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual