Setting 0: Standard
Setting 1: Switch Phase Order
The direction of the motor is reversed.
n
b1-17: Run Command at Power Up
Determines whether an external Run command that is active during power up will start the drive.
No.
Parameter Name
Setting Range
Default
b1-17
Run Command at Power Up
0, 1
1
Setting 0: Disregarded
A new Run command must be issued after power up. Cycle the Run command to start the drive.
Note:
For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at
power up, the AUTO LED will flash quickly.
Setting 1: Allowed
The motor will start immediately after a power up if a Run command is already enabled.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin
rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to
powering up the drive. Failure to comply may cause serious injury.
u
b2: DC Injection Braking and Short Circuit Braking
These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.
n
b2-01: DC Injection Braking Start Frequency
Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).
No.
Name
Setting Range
Default
b2-01
DC Injection Braking Start Frequency
0.0 to 10.0 Hz
Determined by
A1-02
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f (A1-02 = 0)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
Output
frequency
Time
b2-04
DC Injection
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
Figure 1.8 DC Injection Braking at Stop for V/f
Note:
If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.
OLV/PM (A1-02 = 5)
For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. When the output
frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC Injection
Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after Short-Circuit Braking
is complete.
1.2 b: Application
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
29
1
Parameter Details