o2-06: Operation Selection when HOA Keypad is Disconnected
Determines whether the drive will stop when the HOA keypad is removed in HAND mode or when b1-02 or b1-16 is set to
0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
Name
Setting Range
Default
o2-06
Operation Selection when HOA Keypad is Disconnected
0, 1
1
Setting 0: Continue Operation
The operation continues.
Setting 1: Trigger a Fault
The operation stops and triggers an oPr fault. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the HOA
keypad.
Note:
This parameter is effective only when the Run command is set to be given from the HOA keypad (b1-02, b1-16 = 0).
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using Operator
0, 1
0
Setting 0: Forward
Setting 1: Reverse
n
o2-19: Selection of Parameter Write during Uv
Selects whether parameter settings can be changed during a DC bus undervoltage condition. Used with 24 V Power Supply
option (PS-A10LB, PS-A10HB).
No.
Name
Setting Range
Default
o2-19
Selection of Parameter Write during Uv
0, 1
0
Setting 0: Disabled
Setting 1: Enabled
u
o3: Copy Function
These parameters control the Copy function of the HOA keypad. The Copy function stores parameter settings into the memory
of the HOA keypad to facilitate the transfer of those settings to other drives that are the same model, capacity, and same control
mode setting.
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the HOA keypad.
Note:
The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the HOA keypad to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.
1.10 o: Operator-Related Settings
132