Register No.
Contents
00D9H
oFA1
o
Contents (CN5)
bit 0
Option RAM Fault (oFA10)
bit 1
Option Operation Mode Fault (SLMoD) (oFA11)
bit 2
Drive Receive CRC Error (oFA12)
bit 3
Drive Receive Frame Error (oFA13)
bit 4
Drive Receive Abort Error (oFA14)
bit 5
Option Receive CRC Error (oFA15)
bit 6
Option Receive Frame Error (oFA16)
bit 7
Option Receive Abort Error (oFA17)
bit 8 to F
Reserved
00DAH
Reserved
00DBH
oFA3
o
Contents (CN5)
bit 0
Comm. ID Error (oFA30)
bit 1
Model Code Error (oFA31)
bit 2
Sumcheck Error (oFA32)
bit 3
Comm. option timeout waiting for response (oFA33)
bit 4
MEMOBUS Timeout (oFA34)
bit 5
Drive timeout waiting for response (oFA35)
bit 6
CI Check Error (oFA36)
bit 7
Drive timeout waiting for response (oFA37)
bit 8
Control Command Selection Error (oFA38)
bit 9
Drive timeout waiting for response (oFA39)
bit A
Control Response Selection 1 Error (oFA40)
bit B
Drive timeout waiting for response (oFA41)
bit C
Control Response Selection 2 Error (oFA42)
bit D
Control Response Selection Error (oFA43)
bit E, bit F
Reserved
00DCH to 00E9H
Reserved
00EAH
Fault Contents 9
bit 0
Time Not Set (TIM)
bit 1
Oper Battery Low (bAT)
bit 2
Time Data Err (TdE)
bit 3
Time Interval Error (TIE)
bit 4
Overvoltage 2 (ov2)
bit 5
Reserved
bit 6
External Fan Fault (Fn1)
bit 7 to F
Reserved
00EBH to 00FFH
Reserved
0100H to 2FFFH
Reserved
3000H to 3003H
Used for Various Monitors U5-
oo
Refer to U: Monitors on page 232
3004H
Set Time HHMM
3005H
Set Date Year
3006H
Set Date Month Day MMDD
3007H
Set RTC
3008H to 3028H
Used for Various Monitors U2-
oo
, U3-
oo
, U5-
oo
Refer to U: Monitors on page 232
3029H to 302EH
Reserved
302FH
RTC Enter
3030H
RTC Enter Enable
<1> Parameter o1-03, HOA Keypad Display Selection, determines the units.
<2> Communication error contents are saved until the fault is reset.
E.9 MEMOBUS/Modbus Data Table
324
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual