Option: Deployment PROFIBUS communication
9.1 Fast introduction
For the PROFIBUS communication the use of the optionally available extension module
EM M09 is required. The extension module provides interface X2: MPI(PB) with fixed pin
The PROFIBUS DP slave is to be config-
ured in the hardware configurator from Siemens. Here the configuration happens by the
sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X2 MPI(PB) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
storage media - VSD, VSC’ page 98
The configuration of the PROFIBUS DP slave should be done with the following
approach:
n
Activating bus functionality by means of a VSC
n
Hardware configuration - CPU
n
Use as DP slave
–
With activating the bus functionality
‘PROFIBUS DP slave’
by means of a VSC,
the bus functionality
‘PROFIBUS DP slave’
is unlocked.
n
Transfer of the entire project to the CPU
With the Siemens SIMATIC Manager, the CPU M13-CCF0000 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
The PROFIBUS DP slave is to be configured and connected via the sub
module X1 (MPI/DP).
Overview
Steps of configuration
VIPA System MICRO
Option: Deployment PROFIBUS communication
Fast introduction
HB400 | CPU | M13-CCF0000 | en | 18-50