In this area you can configure time-of-day master for time-of-day synchronization in the
network.
Chap. 4.6.1.1.1 ‘Time-of-day synchronization’ page 74
Here you can set the interval time with which "Keep-Alive" telegrams are to be sent to a
connection partner. This ensures that a communication partner can still be reached
because the connection resources are automatically released again after the expiration
interval
time.
7.3.3.3
Port 1
Shown is the short name "Port...". In the field Name another designation may be selected,
which is also shown in the configuration table At
comment
you may describe your entry
near more. The comment also appears in the configuration table.
Via the
port
address the diagnostics information of the IO controller may be accessed.
These parameters serve for the port setting for topology.
These parameters serve for the port setting. Here the following parameters are sup-
ported:
n
Connection
–
Here you can make settings for transmission medium and type. Ensure that the
setting for the local port and the partner port are identical.
–
PROFINET requires 100Mbit/s in duplex mode.
n
Boundaries
–
Boundaries
are limitations for the transfer of certain Ethernet frames. The fol-
lowing
Boundaries
are supported:
‘End of detection of accessible nodes’
: DCP frames for detecting accessible
nodes are not forwarded. When enabled, participants which are lying behind this
port, are no longer recognized and can not be reached by the controller.
‘End of topology discovery’
: When enabled, this port does not support topology
discovery, i.e. LLDP frames are not forwarded.
7.3.4 Configuration PROFINET IO device
The modules, which may be configured here are listed in the hardware catalog.
n
For the deployment of the PROFINET IO devices from VIPA you have to include the
modules into the hardware catalog by means of the GSDML file from VIPA.
n
After the installation of the GSDML file the PROFINET IO devices from VIPA may be
found in the hardware catalog at
‘PROFINET IO
è
Additional field devices
è
I/O
è
VIPA ... ’
Tab: ‘Time-of-day
synchronization’
Tab: ‘Options’
Interval
Tab: ‘General’
Tab: ‘Addresses’
Tab: ‘Topology’
Tab: ‘Options’
Precondition
VIPA System MICRO
Deployment PG/OP communication - PROFINET
Deployment as PROFINET IO controller > Configuration PROFINET IO device
HB400 | CPU | M13-CCF0000 | en | 18-50