7.7 Device replacement without exchangeable medium/PG
IO devices, which support the PROFINET function
Device replacement without
exchangeable medium/PG
get their device name from the controller with the exchange.
These can be replaced without installing an "exchangeable medium" (memory card) with
the stored device name respectively without assigning a device name by a PG. To assign
the device name the IO controller uses the configured
Topology
and the "neighbourhood
relationship", which is determined by the IO devices.
Thus the
Device replacement without exchangeable medium/PG
is possible, the following
requirements must be met:
n
The
Topology
of your PROFINET IO system with the corresponding IO devices must
be configured.
n
The IO controller and the respective adjacent to the unit to be replaced IO device
must support the functionality
Device replacement without exchangeable medium/PG
.
n
In the IO controller in the
‘Properties’
the option
Support device replacement without
exchangeable medium
must be enabled.
n
The replaced device must be reset to delivery state, before.
The configuration of the function
Device replacement without exchangeable medium/PG
in your PROFINET IO system happens with the following approach:
1.
Double-click at the PROFINET interface of the IO controller of the CPU.
ð
The properties dialog of this PROFINET interface is opened
2.
Enable in the register
‘General’
the option
‘Support device replacement without
exchangeable medium’
.
3.
Apply the settings with [OK].
4.
Safe and translate the hardware configuration.
5.
Configure your
Topology.
6.
Transfer your project to the CPU.
For the replacement the "replace device" must be in "delivery state". If you have not
received a new "replace device" from VIPA, you have to prepare this with the following
approach:
1.
For this connect your "replace device" local at your PG.
2.
Start the Siemens SIMATIC Manager and execute
‘PLC
è
Edit Ethernet node’
3.
Click at
‘Nodes accessible online’
at [Browse].
4.
Select the according IO device, which you identify as your "replace device".
5.
Click at
‘Reset to factory settings’
at [Reset].
ð
Your IO device is now reset and has then "delivery state".
For the replacement the "replace device" must be in "delivery state".
1.
Disconnect if not already done your device to be exchanged from power.
2.
Replace this by your "replace device".
3.
Connect the "replaced device" to power and turn it ON.
ð
Here by comparison of target and current topology, the "replaced device" is
automatically detected by the IO controller and automatically integrated to the
user data traffic.
Overview
Configuring the function
Prepare the replace device
Replace device
VIPA System MICRO
Deployment PG/OP communication - PROFINET
Device replacement without exchangeable medium/PG
HB400 | CPU | M13-CCF0000 | en | 18-50