4 ... 20mA
Output range
Current
(I)
Decimal
(D)
Hex
Range
Formulas
4 ... 20mA
> 22.81mA
32767
7FFFh
overflow
22.81mA
32511
7EFFh
overdrive range
20mA
27648
6C00h
nominal range
12mA
13824
3600h
4mA
0
0000h
1.185mA
-4864
ED00h
underdrive range
< 1.185mA
-32768
8000h
underflow
0 ... 600Ω
0 ... 600Ω
Resistance
(R)
Decimal
(D)
Hex
Range
Formulas
0 ... 600Ω
> 705.53Ω
32767
7FFFh
overflow
705.53Ω
32511
7EFFh
overdrive range
600Ω
27648
6C00h
nominal range
0Ω
0
0000h
(negative values are physically not possible)
underdrive range
With Pt 100 the temperature is directly shown with the adjusted unit. Here applies: 1 Digit
= 0.1 temperature unit
Pt100
Dec (D)
Hex
Pt100
Dec (D)
Hex
Pt100
Dec(D)
Hex
Range
in °C (1digit=0.1°C)
in °F (1digit=0.1°F)
in K (1digit=0.1K)
>1000.0
32767
7FFFh
>1832.0
32767
7FFFh
>1273.2
32767
7FFFh
overflow
1000.0
10000
2710h
1832.0
18320
4790h
1273.2
12732
31BCh
overdrive range
850.0
8500
2134h
1562.0
15620
3D04h
1123.2
11232
2BE0h
nominal range
-200.0
-2000
F830h
-328.0
-3280
F330h
73.2
732
2DCh
-243.0
-2430
F682h
-405.4
-4054
F02Ah
30.2
302
12Eh
underdrive
range
<-243.0
-32768
8000h
<-405.4
-32768
8000h
<30.2
32768
8000h
underflow
Current measurement
Resistance
Resistance thermometer
Pt100 Standard
VIPA System 300S
+
Deployment I/O periphery
Analog part > Analog value representation
HB140 | CPU-SC | 313-5BF23 | en | 19-01
97