No.
Name
Description
Range
H2: Multi-Function Digital Outputs
Use H2 parameters to assign functions to the multi-function digital outputs.
H2-01
Terminal MA, MB and MC Function Selection (relay)
Refer to “Multi-Function Digital
Output Selection Table” for a
description of setting values.
0 to 192
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
H2-06
Watt Hour Output Unit Selection
Refer to V1000 Tech Manual.
0 to 4
H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
Description
0
During Run
Closed: A Run command is active or voltage is output.
1
Zero Speed
Closed: Output frequency is 0.
2
Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus the
hysteresis set to L4-02).
3
User Set Speed Agree 1
Closed: Output frequency and speed reference equal the value in L4-01
(plus or minus the hysteresis of L4-02).
4
Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with
hysteresis determined by L4-02.
5
Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in L4-01,
with hysteresis determined by L4-02.
6
Drive Ready
Closed: Drive Ready. The drive is powered up, not in a fault state, and
in the Drive mode.
7
DC Bus Undervoltage
Closed: DC bus voltage is below the UV trip level set in L2-05.
8
During Baseblock (N.O.)
Closed: This is no output voltage
9
Frequency Reference Source
Closed: Digital operator supplies the frequency reference.
A
Run Command Source
Open: Reference 1 or 2 are active
Closed: Digital operator supplies the run command.
B
Torque Detection 1 (N.O.)
Closed: Output current/torque exceeds the torque value set in parameter
L6-02 for longer than the time set in parameter L6-03.
C
Frequency Reference Loss
Closed: Loss of the analog frequency reference detected. Enabled when
L4-05 = 1.
D
Braking Resistor Fault
Closed: Braking resistor or transistor is overheated or faulted out.
E
Fault
Closed: Fault occurred (other than CPF00 and CPF01).
F
Not used/Through Mode
Set this value when the terminal is not used, or when using the terminal
in the pass-through mode.
10
Alarm
Closed: An alarm is triggered.
11
Reset Command Active
Closed: Reset command to the drive is active.
12
Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction with
the digital input (H1-
= 18 “timer function”).
B.1 Parameter Table
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
185
B
Parameter List