u
Setting 4: HVAC Fan Application
Table 4.9 HVAC Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C6-01
Drive Duty Selection
1: Normal Duty
C6-02
Carrier Frequency Selection
3: 8.0 kHz
H2-03
Terminals P2 Function Selection
39: Watt Hour Pulse Output
L2-01
Momentary Power Loss Operation
Selection
2: CPU Power Active - Drive will restart if
power returns prior to control power supply
shut down.
L8-03
Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
L8-38
Carrier Frequency Reduction
2: Enabled across entire frequency range.
Table 4.10 HVAC Fan: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-03 V/f Pattern Selection
b1-02
Run Command Selection 1
E1-04 Maximum Output Frequency
b1-04
Reverse Operation Selection
E2-01 Motor Rated Current
C1-01 Acceleration Time 1
H3-11 Terminal A2 Gain Setting
C1-02 Deceleration Time 1
H3-12 Terminal A2 Bias Setting
C6-02 Carrier Frequency Selection
L2-01 Momentary Power Loss Operation
Selection
d2-01
Frequency Reference Upper Limit
L8-03 Overheat Pre-Alarm Operation Selection
d2-02
Frequency Reference Lower Limit
o4-12
kWh Monitor Initialization
u
Setting 5: Compressor Application
Table 4.11 Compressor: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C1-01
Acceleration Time 1
5.0 s
C1-02
Deceleration Time 1
5.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
4.5 Application Selection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
99
4
Start-Up Programming & Operation
Содержание PROFINET V1000
Страница 1: ......
Страница 230: ...This Page Intentionally Blank 230 YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive V1000 Quick Start Guide...