6.4 Precautions on Wiring
6-37
6
Although the capacity of the surge absorber used must be adjusted to the load, the
following surge absorber is recommended for general applications:
• CR50500 (manufactured by Okaya Electric Industries Co., Ltd.) or equivalent.
Fig. 6.15 Connecting Contacts to an Inductive Load
4) Maximum Load Current
Although a 0.6-A load can be connected to each output point for AC 16-point Output
Module, the total load must be 2.4 A or less for each common. Keep the maximum
load at 2.4-A for each common.
If this limit is exceeded, damage may occur to the output circuit.
Fig. 6.16 Maximum Load Current
100 VAC
(200 VAC)
Surge absorber
Inductive
load
Output
Output
Common
1-1
Common
1-2
Load
CAUTION
0.6 A/point
Fuses
Output 1
Common 1-2
Common 1-1
Fuse
2.4 A/common
100 VAC
(200 VAC)
Loads
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2