4.3 I/O Allocation
4-37
4
(3) Service Scan: Normal/High-speed
Two types of service scans are available:
normal
and
high-speed
. A service scan
is recommended when using the high-speed segment function. The I/O module is
activated before the ladder decoding of the high-speed segments. The I/Os that are
processed in synchronization with the high-speed scan are called
High-speed Seg-
ment I/Os
. The MEMOSOFT is set by default to “
NORMAL
.”
d) Input Signal Status
Error signals are generated by the Analog Input Module when an input signal
exceeds the input signal range.
(1) Analog Input Module (
±
10 V, 4 channels)
Input Register
Application
n
Analog input signal status for channels 1 to 4
Bit 15
1 when +10.24 V < channel 4 input signal
Bit 14
1 when +10.24 V < channel 3 input signal
Bit 13
1 when +10.24 V < channel 2 input signal
Bit 12
1 when +10.24 V < channel 1 input signal
Bit 11
1 when +10.0 V < channel 4 input signal < +10.24 V
Bit 10
1 when +10.0 V < channel 3 input signal < +10.24 V
Bit 9
1 when +10.0 V < channel 2 input signal < +10.24 V
Bit 8
1 when +10.0 V < channel 1 input signal < +10.24 V
Bit 7
1 when -10.24 V < channel 4 input signal < -10.0 V
Bit 6
1 when -10.24 V < channel 3 input signal < -10.0 V
Bit 5
1 when -10.24 V < channel 2 input signal < -10.0 V
Bit 4
1 when -10.24 V < channel 1 input signal < -10.0 V
Bit 3
1 when channel 4 input signal < -10.24 V
Bit 2
1 when channel 3 input signal < -10.24 V
Bit 1
1 when channel 2 input signal < -10.24 V
Bit 0
1 when channel 1 input signal < -10.24 V