4.2 Analog Output Specifications
4-21
4
2) Output Characteristics
The following diagram show the output characteristics. Two modes are available:
±
2000 mode and 0-4000 mode. The mode is selected by I/O allocation.
Note: (1)
For
±
2000 mode, if output register value exceeds the range from
-2000 to +2000, the analog output value will be clamped at -
10.00 or +10.00 V.
(2)
For 0-4000 mode, if output register value exceeds the range from
0 to 4000, the analog output value will be clamped at -10.00 or
+10.00 V.
Approximate Mass
350 g
External Dimensions
40.3
×
130
×
103.9 mm (W
×
H
×
D)
Recommended Cable
Shielded twisted-pair wires
1.3 mm
2
(AWG16) to 0.5 mm
2
(AWG20)
Item
Specification
Output register value
Analog output value
±
2000 mode
0-4000 mode
≤
-2000
-10.00 V
-10.00 V
-1000
-5.00 V
-10.00 V
0000
0.00 V
-10.00 V
+1000
+5.00 V
-5.00 V
+2000
+10.00 V
0.00 V
+3000
+10.00 V
+5.00 V
≥
+4000
+10.00 V
+10.00 V
Analog output value(V)
Output register value
+2000 mode
10
5
0
-5
-10
0
1000
2000
-1000
-2000
Analog output value(V)
Output register value
0-4000 mode
10
5
0
-5
-10
2000
3000
4000
1000
0