4 Analog I/O Specifications
4.2.2 Analog Output Modules (0 to 10 V, 2 channels) (0 to 5 V, 2 channels)
4-26
2) Output Characteristics
The following diagram shows the output characteristics.
a) Output characteristics for 0 to 10 V, 2CH
b) Output characteristics for 0 to 5 V, 2CH
Note: (1)
For 0 to 10 V (2 channels), an output register value exceeding
the range of 0 to 4000 will be clamped at 0 or 10.0 V.
(2)
For 0 to 5 V (2 channels), an output register value exceeding the
range of 0 to 4000 will be clamped at 0 or 5.0 V.
Output register value
Analog output value
±
2000 mode
0-4000 mode
≤
0000
0.00 V
0.00 V
+1000
+2.50 V
+1.25 V
+2000
+5.00 V
+2.50 V
+3000
+7.50 V
+3.75 V
≥
+4000
+10.00 V
+5.00 V
Analog output value(V)
Output register value
Analog output value(V)
Output register value