4 Analog I/O Specifications
4.3.1 Analog Input Modules
4-38
(2) Analog Input Module (0 to10 V, 4 channels)
(3) Analog Input Module (4 to 20 mA, 4 channels)
Input Register
Application
n
Analog input signal status for channels 1 to 4
Bit 15
1 when +10.12 V < channel 4 input signal
Bit 14
1 when +10.12 V < channel 3 input signal
Bit 13
1 when +10.12 V < channel 2 input signal
Bit 12
1 when +10.12 V < channel 1 input signal
Bit 11
1 when +10.0 V < channel 4 input signal < +10.12 V
Bit 10
1 when +10.0 V < channel 3 input signal < +10.12 V
Bit 9
1 when +10.0 V < channel 2 input signal < +10.12 V
Bit 8
1 when +10.0 V < channel 1 input signal < +10.12 V
Bit 7
Not used.
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Input Register
Application
n
Analog input signal status for channels 1 to 4
Bit 15
1 when 20.48 mA < channel 4 input signal
Bit 14
1 when 20.48 mA < channel 3 input signal
Bit 13
1 when 20.48 mA < channel 2 input signal
Bit 12
1 when 20.48 mA < channel 1 input signal
Bit 11
1 when 20.0 mA < channel 4 input signal < 20.48 mA
Bit 10
1 when 20.0 mA < channel 3 input signal < 20.48 mA
Bit 9
1 when 20.0 mA < channel 2 input signal < 20.48 mA
Bit 8
1 when 20.0 mA < channel 1 input signal < 20.48 mA
Bit 7
1 when 2.0 mA < channel 4 input signal < 4.0 mA
Bit 6
1 when 2.0 mA < channel 3 input signal < 4.0 mA
Bit 5
1 when 2.0 mA < channel 2 input signal < 4.0 mA
Bit 4
1 when 2.0 mA < channel 1 input signal < 4.0 mA
Bit 3
1 when channel 4 input signal < 2.0 mA
Bit 2
1 when channel 3 input signal < 2.0 mA
Bit 1
1 when channel 2 input signal < 2.0 mA
Bit 0
1 when channel 1 input signal < 2.0 mA