7 Alarm and Warning Processing
7.6.1 Emergency Stop and Main Circuit Magnetic Contactor Control Settings
7-14
• Power regeneration converter: Software version 0008 or higher
• SERVOPACK: Software version 000B or higher
If the above versions are not used, the following alarm will occur.
7.6.1
Emergency Stop and Main Circuit Magnetic Contactor Control Settings
(1) Emergency Stop Selection
Set SERVOPACK parameter Pn01B to select whether to use the emergency stop function.
This setting is required for each axis individually.
(2) Main Circuit Magnetic Contactor Control Selection
Set SERVOPACK parameter Pn01B to select whether to use main circuit magnetic contactor control.
This setting is required for each axis individually.
∗
For a SERVOPACK for two axes (CACR-JUM
), this setting is required only for the first axis.
If the settings for the first and second axes do not match, only the setting for the first axis is used.
(3) Emergency Stop Torque
When an emergency stop is performed, the motor decelerates to a stop. The deceleration torque used at this
time is set in parameter Pn406.
Note 1. For a spindle axis, set the instantaneous peak torque for the spindle motor to 120%.
2. For a feed axis, the deceleration torque when overtravel occurs is also the value that is set for parameter Pn406.
3. For a spindle axis, the deceleration torque when overtravel occurs is the value that is set in parameter Pn430
(powering) and Pn431 (regeneration).
Alarm
Code
Alarm Name
Description
Alarm Stop
Method
Reset
A.05B
Converter Combination
Error
This alarm occurs when there is a
problem with the combination of
the power regeneration converter
and SERVOPACK.
Gr.1
Required
Parameter
Meaning
When Enabled
Classification
Pn01B
n.
0
(factory setting)
Disables the emergency stop func-
tion.
After restart
Setup
n.
1
Enables the emergency stop func-
tion.
Parameter
Meaning
When Enabled
Classification
Pn01B
*
n.
0
(factory setting)
Disables main circuit magnetic
contactor control.
After restart
Setup
n.
1
Enables main circuit magnetic con-
tactor control.
Parameter
Setting Range
Setting Unit
Factory Setting
When Enabled
Classification
Pn406
0 to 800%
1%
800%
Immediately
Setup