Xtreme Power Conversion Corporation
G90 User’s Manual
Page 52
Uninterruptible Power Supply
WARNING!
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Replacing EBPs
CAUTION!
The EBP is heavy. Lifting the cabinet requires a minimum of two people.
1.
If the battery fault, the following steps are provided for modular unit to replace the new battery pack.
2.
Remove the front panel of the battery box.
3.
Remove the connection cables between battery box and UPS. Release the screw of the baffle of the bat-
tery pack as the figure below shows, then remove the baffle from the left.
4. Grasp the handle in front of the battery pack, take out of it and hold it, then remove the battery pack.