Xtreme Power Conversion Corporation
G90 User’s Manual
Page 30
Uninterruptible Power Supply
2 - Bypass function setting
1.
Enter the setting interface. Press
and hold the function setting but-
ton
for more than 2 seconds
stepping through using the scroll
button
until reaching the
“bPS” flashing.
2.
Enter the BPS setting interface.
Press and hold the function setting
button
for more than ½ sec-
ond (less than 2 seconds). At this
time the “bPS” will stop flashing.
The “ON” (or OFF) below the bPS
will flash. Press and hold the scroll
key
for more than ½ second
(less than 2 seconds) to determine
whether the BPS function is en-
abled or disabled.
3.
Confirm the BPS selecting inter-
face. After selecting ON or OFF,
press and hold the function setting
button
for more than ½ sec-
ond (less than 2 seconds). Now the
BPS setting function is completed
and the “ON” of “OFF” below the
“bPS” will light without flashing.
4. If “OFF” is chosen go to step 7,
otherwise go to step 5.
5.
Set the BPS tolerance range. Briefly
press the scroll button
or
for more than ½ second
(less than 2 seconds) to select
the voltage range in percentage
+5%,+10%,+15%,+25%(default),
then briefly press the function
setting button
for more than
½ second (less than 2 seconds) to
confirm selection.
6. Then set the minus range in a simi-
lar manner.
7. After the minus range is confirmed,
press the function setting button
for more than 2 seconds to
exit setting menu.