Xtreme Power Conversion Corporation
G90 User’s Manual
Page 18
Uninterruptible Power Supply
Tighten four M5 Umbrella Nuts in the side of rail assembly
Fix one rail assembly to the front of the rack with one M5 x 12 pan-head screw and one M5 cage nut. Use two M5
cage nuts and two M5 x 12 pan-head screws to fix the rail assembly to the rear of the rack.
Tighten all screws and nuts.
Repeat steps for the other rail assemblies.
Step 3
Place the UPS or EBP on a flat, stable surface with the front of the UPS or EBP facing you.
Align the mounting brackets with the screw holes on each side of the UPS or EBP and fix with supplied M4 x 8 flat-
head screws.
Slide the UPS or EBP into the rack.
Secure the front of the UPS to the rack using one M5 x 12 pan-head screw and one M5 cage nut on each side.
Install the bottom screw on each side through the bottom hoes of the mounting bracket and the bottom hole of
the rail.