Xtreme Power Conversion Corporation
G90 User’s Manual
Page 39
Uninterruptible Power Supply
UPSILON2000 Power Management Software
Each UPS ships with UPSilon2000 Power Management Software. To begin installation of UPSilon2000 software, see
the instructions accompanying the Software Suite CD.
Note: Install UPSilon2000 power management software with the serial number attached on the cover of the CD.
When running the monitoring software, choose appropriate communications port.
If using RS232, choose COM1/2 and Megatec protocol.
If using USB, choose Megatec USB.
UPSilon2000 software provides up-to-date graphics of UPS power and system data and power flow. It also gives
you a complete record of critical power events, and it notifies user of important UPS or power information. If there
is a power outage and the UPS battery power becomes low, UPSilon2000 software can automatically shut down
the computer system to protect the data before the UPS shutdown occurs.
Troubleshooting
The following messages are the information that users would find on the UPS when problems are experienced.
The user can judge if the fault is caused by external factors and determine how to deal with the problem by using
this information.
If the Fault LED is on, it indicates that the UPS had detected some faults. The buzzer beeps to indicate that the
UPS needs to be checked - if beeping continues it indicates that there is something wrong with the UPS requiring
service. Please contact the service department for assistance.
Fault
Cause
Solution
The “INPUT” letters on LCD display
section flashing
The input utility is not connected or
is out of range
Re-connect the input power cable
and check to be sure input power is
available
Battery capacity indicator flashing
Battery low voltage or battery dis-
connected
Check UPS battery, connect bat-
tery securely, if battery is damaged,
replace
Utility normal but UPS has no input UPS input breaker open circuit
Press the breaker for reset
Short backup time
Battery not fully charged
Keep UPS connected with utility
power for more than 8 hours to
recharge battery
UPS overload
Check loads connected and remove
some non-critical loads
Battery aged
When replacing the battery, please
contact dealer or distributor to get
the correct battery and/or assis-
tance