Power Supply
VESDA Sensepoint XCL requires an isolated power supply unit that is certified by a national or international
standard, such as UL.
Specification
Value
Nominal DC input voltage
24 V DC
1
Nominal AC input voltage
24 V AC
2
, 50/60 Hz
Inrush current
Less than 850 mA
Outputs
Specification
Value
Analog output
0 to 22 mA sink or source (configurable)
Digital output
Modbus RTU
Relay output
5 A, 250 V AC, 24 V DC
The two relays can be used for fault signaling (normally energized) or for alarm signaling. The relay
assignments and operations are configurable using the Sensepoint App.
l
Modbus RTU Default Communication Setting
Specification
Value
Baud rate
9600 bps
Parity
Even
Data bits
8
Stop bits
2
Flow control
None
Refer to Appendix A.6 for details on the Modbus registers. Adjustable Modbus settings:
l
Slave ID: 1 to 255
l
Baud rate: 9600, 19200 bps
l
Parity: None, Even, Odd
l
Relay Default Setting
Specification
Value
Relay 1
Any faults and initial state is energized.
Relay 2
Gas alarm 1 and initial state is de-energized.
Maximum Power Consumption
The power consumption varies, depending on output version and sensor type. The additional maximum power
consumption for the relay output version is 0.6 W.
l
Analog Output Version
In normal state
During an alarm
Electrochemical-cell-type sensor
(CO, H
2
, H
2
S, NO
2
, NH3, O
2
)
0.5 W
1.2 W
Catalytic-type sensors (CAT)
1.0 W
1.7 W
Infrared-type sensors (CO
2
)
1.0 W
1.7 W
l
Digital Output Version
In normal state
During an alarm
Electrochemical-cell-type sensor
(CO, H
2
, H
2
S, NO
2
, NH
3
, O
2
)
0.3 W
0.7 W
Catalytic-type sensors (CAT)
0.8 W
1.2 W
Infrared-type sensors (CO
2
)
0.8 W
1.2 W
1
mA versions: 11 to 32 V DC, Modbus versions: 9 to 32 V DC
2
20 to 27 V A