VESDA Sensepoint XCL – Large Bore Installation Manual
35563_02
34
A.2
Troubleshooting
1. Warning
Description
Troubleshooting
Warning 1 Calibration Overdue
Calibrate the unit.
Warning 3 BLE failure
(BLE version only)
Power-cycle the unit. If same warning occurs again, contact
manufacturer.
Warning 4 Time/date not set (RTC not set) /
RTC reset abnormally
Configure unit time. If same warning occurs again, contact
manufacturer.
Warning 5 Log memory corrupted
(CRC not matched)
Power-cycle the unit. Event log might be lost.
Warning 6 Certificate is corrupted or missing
certificate
Contact manufacturer.
Warning 7 Over-range warning
Calibrate the unit.
Warning 8 Under-range warning
Calibrate the unit.
2. Fault
Description
Troubleshooting
Fault 1
Internal communication
failure
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 2
Cell failure
Check the sensor connection. If same fault occurs again, replace
sensor.
Fault 3
Cell is producing a
negative reading
Calibrate the unit.
Fault 4
EEPROM is corrupted
Reconfigure the unit by using Sensepoint App. If same fault occurs
again, contact manufacturer.
Fault 5
MCU operating voltage
failure
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 6
RAM read/write fault
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 7
Flash memory corrupted
Reconfigure the unit by using Sensepoint App.
Fault 8
Code memory failure
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 9
mA output failure (mA
output version only)
Check whether loopback resistor is connected correctly.
Fault 10
Supplied voltage failure
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 11
Internal HW Fault
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 12
Internal SW Fault
Power-cycle the unit. If same fault occurs again, contact
manufacturer.
Fault 13
Calibration Overdue
Calibrate the unit.