Modbus
Register
Address
Information
R/W
Type
Size
Description
Notes
40146 to
40152
Gas Name String
R
string[14] 7
String of gas name which is configured by user
40153
Temperature (°C)
R
s16
1
Transmitter temperature, duplicate
40154
Temperature (°F)
R
s16
1
40155
Calibration Due
R
s16
1
This indicates the time remaining days before the ECC
sensor must be calibrated or replaced. Calibration
interval - DaysPassedSinceLastSuccessfulCal
40156
Relay Status
R
u8
1
l
High nibble : Relay 2 status
l
Low nibble : Relay 1 status
l
1 : Energized, 0 : De-energized
40157 to
40158
SuppliedVoltage
R
f32
2
The voltage supplied to the device at the nominal 24.0
volt input, in millivolts.
40159
Calibration Interval
R
u16
1
Gas calibration interval in days
40160
Alarm type
R
u8
1
For example:
If A1:rising/A2:rising -> 0x11, 0b00010001
If A1:rising/A2:falling -> 0x21 0b00100001
l
High nibble : Alarm 2 Type
l
Low nibble : Alarm 1 Type
l
0: Disable, 1: Rising, 2:Falling
40161
Reserved
40162
Relay Configuration
R
u8
1
For example:
Relay1 to Alarm 1 (01)
Relay2 to Alarm 2 (10)
Initial relay1 status to De-energized (0)
Initial relay2 status to Energized (1)
Then, the bits are 0b00101001, which is 0x29
l
Bit: 0 to 1: Relay Type 1 (0: Fault, 1: Alarm1, 2: Alarm2)
l
Bit: 2 to 3: Relay Type 2 (0:Fault, 1: Alarm1, 2: Alarm2)
l
Bit: 4 : Initial Relay Status 1 (0: De-energized, 1:
Energized)
l
Bit: 5 : Initial Relay Status 2 (0: De-energized, 1:
Energized)
l
Bit:7 ~8: not in use
40163
Relay On Delay Time
R
u16
1
Delay between allocated trigger occuring and actual
relay activation
Unit : seconds
40164
Relay Off Delay Time
R
u16
1
Delay between allocated trigger ceasing and actual
relay release
Unit : seconds
40165 to
40166
User configured full
scale range
R
f 32
2
Display Range (Fulls Scale)
40167 to
40168
Alarm Threshold 1
R
f 32
2
VESDA
VESDA Sensepoint XCL – Large Bore Installation Manual
www.xtralis.com
42