Replacing the Sensor Cover
Warning:
Use only genuine replacement sensor cover specifically for use with VESDA Sensepoint XCL.
Attempting to use non-genuine sensor cover could result in malfunction of the product.
1. Disable smoke detector to prevent the transmission of potential flow fault alarm.
2. Disconnect both sampling pipes and remove the Flow Cap from the detector.
3. Remove the sensor cover (loosen the screw on the top of the sensor cover).
4. Replace the sensor cover and secure with the screw, taking care not to over-tighten it.
5. Secure the sampling pipe and the Flow Cap to the detector.
6. Enable the smoke detector.
7. Perform calibration (section “4.3 Calibration”).