Gas Leak Detection GLD

Page 1 of 4

Description

The GLD gas leak detection range is suitable for use in Boiler 

Rooms and other Commercial applications to provide safety and 

shut down functions in the event of gas leakage.
Control units are available in 1, 2 or 3 channels for connection to 

1, 2 or 3 remote sensors. They are mounted in DIN rail housings 

with the option of panel or wall mount enclosures. 
Output relays to operate auxiliary devices such as Solenoid Gas 

Valves or  Sirens and fault remote signalling are fitted to all units.

Power supply is 230Vac or 12-24Vdc and sensors are available 

for both  Natural Gas, LPG/Propane and Carbon Monoxide.

Features

1, 2 & 3 channel options

 

Audio & visual alarms

 

Adjustable alarm sensitivity

 

Relay output for gas valves

 

Relay outputs for remote alarms

 

Auto or manual reset

 

Technical Specification

Power Supply:

 

GLD361: 230Vac ±10% @ 50Hz

 

GLD65*: 12V ±10% 

Power Consumption:

  GLD361: 3VA

 

GLD65*: 7VA

Relay Outputs:

 

GLD361: 5(1)A @ 250V SPDT

 

GLD65*: 2 x 5(1)a @ 250V SPDT

Pre-alarm Thresholds:

 

Natural Gas:

 0.3% to 0.8% 

 

 

 

(3000 to 8000ppm)

 

LPG:

 

0.14% to 0.35% 

 

 

 

(1400 to 3500ppm)

 

CO: 

 

0.012% to 0.03%    

 

 

 

(120 to 300ppm)

Alarm Thresholds:

 

Natural Gas:

 0.5% to 1.25% 

 

 

 

(5000 to 12500ppm)

 

LPG:

 

0.22% to 0.56% 

 

 

 

(2200 to 5600ppm)

 

CO: 

 

0.02% to 0.05% 

 

 

 

(200 to 500ppm)

Sensors:

 

Natural Gas

: GLD150

 

LPG:

 

GLD250

 

CO: 

 

GLD350

Materials:

 

Base – Nylon, Cover – ABS

Ambient:

 

Storage:

 

-25°C to +60°C

 

Operating:

  0°C to +45°C

Order Codes

GLD361

 

DIN rail Single Channel Gas Leak Detection Controller

GLD651

  DIN rail Single Channel Gas Leak Detection Controller

GLD652

  DIN rail Two Channel Gas Leak Detection Controller

GLD653

  DIN rail Three Channel Gas Leak Detection Controller

GLD655

  Panel Mounting Kit

GLD150

  Natural Gas Sensor

GLD250

  Propane/LPG Sensor

GLD350

  Carbon Monoxide Sensor

Installation

Detector

The detector must be sited in a dry space in which the relevant 

ambient limits shown in the Technical Specification are observed. 

If sited in a space classified as “Dangerous” it must be installed 

in a cabinet for electrical devices constructed according to the 

regulations in force for the danger class involved.
The controller can be installed on a DIN rail or in a DIN 

modular enclosure.

Sensors

The correct siting of the sensors is essential for efficient 

operation and depends on the type of gas to be monitored and 

its density in respect of air:
Methane-natural gas (light): 10…50 cm from the ceiling

LPG-propane (heavy): 10…50 cm. from the floor
CO-carbon monoxide: 150…200 cm. from the floor

It is advisable to position the sensors at a certain distance from 

the gas appliances so as to avoid triggering unnecessary alarms:

Boilers & calorifiers : 1…2 meters

Gas cookers : 2…3 meters

Shut-off solenoid valve

This must be installed on the gas feed pipe, possibly 

outside the 

space controlled, in a place which is easily accessible and is 

protected from bad weather.

In LPG installations the valve must be installed 

downstream of 

the pressure reducing valve

 (30 ... 40 mbar).

Summary of Contents for GLD361

Page 1: ...pm Alarm Thresholds Natural Gas 0 5 to 1 25 5000 to 12500ppm LPG 0 22 to 0 56 2200 to 5600ppm CO 0 02 to 0 05 200 to 500ppm Sensors Natural Gas GLD150 LPG GLD250 CO GLD350 Materials Base Nylon Cover ABS Ambient Storage 25 C to 60 C Operating 0 C to 45 C Order Codes GLD361 DIN rail Single Channel Gas Leak Detection Controller GLD651 DIN rail Single Channel Gas Leak Detection Controller GLD652 DIN r...

Page 2: ...more than two cables in a single 7 terminal of the detector and if necessary to use external junction boxes GLD361 B Gas sensor Y1 N O solenoid valve with manual reset Y2 N C solenoid valve Y3 N C solenoid valve with manual reset M Aeration fan Link functions M F1 without link internal buzzer enabled with link internal buzzer disabled F2 F3 without link relay normally energised in presence of gas ...

Page 3: ... This permits in the event of an alarm taking action under conditions of maximum safety Using the SENSITIVITY 1 potentiometer the thresholds can be adjusted within the limits established by the manufacturing standards Potentiometer towards increase in sensitivity Potentiometer towards decrease in sensitivity Alarm The alarm status brings about the action of the operational relay if normally de ene...

Page 4: ...he gas concentration reaches the pre alarm threshold the ALARM 4 LED blinks When it reaches the alarm threshold after a delay of about 20 seconds the ALARM 4 LED lights and remains lit the internal buzzer sounds only if terminals M F1 are without link the operational relay closes the shut off valve or switches on an aeration fan Stop releasing gas when the gas concentration near the sensor falls b...