Configuring the Auxiliary Output
975-0400-01-01
3–13
Trigger Source
Low Batt Voltage
Low Batt
Voltage,
Hi Batt Voltage,
Hi Array Voltage,
Low Batt Temp,
Hi Batt Temp, Hi
Heat Sink Temp,
Fault
Low
Batt
Voltage
Selects the desired condition to
activate the Aux Output.
Trigger 10.0
Clear
12.0
Depends on Trigger
Source (see Table 3-6)
Line 1:
Selects the battery or array
voltage to activate Aux Output. If
the selected Trigger Source is Hi
Batt Temp, Low Batt Temp, or Hi
Heat Sink Temp, this screen
displays Trigger Temperature
Level in degrees Celsius.
Line 2:
Selects the battery or array
voltage to turn off the Aux Output.
If the selected Trigger Source is Hi
Batt Temp, Low Batt Temp, or Hi
Heat Sink Temp, this screen
displays Clear Temperature Level
in degrees Celsius.
This screen is hidden if the trigger
source is set to Fault.
Trig Delay 00:00
Clr Delay 00:00
00:00–09:59
(mm:ss format)
00:00
Line 1:
Selects how long the
selected trigger source must be
active before the Aux Output
activates. This can avoid
unnecessary triggering by
momentary loads.
Line 2:
Selects how long the
trigger condition must remain
inactive before the Aux Output
turns off.
This screen is hidden if the trigger
source is set to Fault.
Output Level
12V
5V–13V
12V
Selects the active high auxiliary
output voltage (the active low
output voltage is 0 V).
Output Mode
Active Hi
Active Hi,
Active Lo
Active
Hi
Sets the mode (polarity) of the aux
output. When Active Hi is
selected, the aux output turns on
when the trigger source is present.
When Active Lo is selected, the
aux output turns off when the
trigger source is present.
Table 3-5
Aux Menu Values
Setting
Values
Default Description