Specifications
A–2
975-0400-01-01
Electrical Specifications
Default Battery Charging Settings
All settings in the following table are based on a 12-volt nominal battery bank.
For the other nominal voltages, scale the values in this table appropriately (48-volt
systems would use voltages four times that of the values listed in this table). An
exception to this is for equalize voltage on a 60-volt system. The maximum
programmable output voltage is 72 volts, but a 60-volt system would need to be
equalized at 80 volts. Therefore, the maximum equalize voltage is limited to
72 volts on a 60-volt system.
Maximum PV Array Voltage (Operating)
140 Vdc
Maximum PV Array Open Circuit Voltage 150 Vdc
Array Short Circuit Current
60 Adc maximum
Nominal Battery Voltage
12, 24, 36, 48, 60 Vdc
Battery Voltage Range (Operating)
10 Vdc to 80 Vdc
Maximum Output Current
60 A (for all battery voltages except 60 V)
Maximum Output Power
3500 W
Auxiliary Output
5–13 V, up to 200 mA
Tare Loss/Night-time Power Consumption 2.5 W
Charger Regulation Method
Three-stage (bulk, absorption, float)
Two-stage (bulk, absorption)
Setting
Battery Type
Flooded
a
a.When a Custom battery type is selected, the default set-
tings are based on the Flooded battery type.
Gel
AGM
Equalize Voltage
16.0V
n/a
n/a
ReCharge Voltage
12.5 V
12.5 V
12.5 V
Bulk Voltage
14.4 V
14.2 V
14.3 V
Absorption Voltage
14.4 V
14.2 V
14.3 V
Float Voltage
13.5 V
13.8 V
13.4 V
Absorption Time
180 min
180 min
180 min
Batt Temp Comp
-27mV/C
-27mV/C
-21mV/C