Configuring the Auxiliary Output
975-0400-01-01
3–15
Hi Batt Temp
Activates the auxiliary output when the battery temperature rises
above the trigger setting for the trigger delay time. Deactivates the auxiliary
output when the battery temperature falls below the clear setting for the clear
delay time. Battery temperature is measured with a battery temperature sensor. Do
not use this setting if a battery temperature sensor is not installed. With this
setting, the auxiliary output can turn on a fan to cool the battery compartment.
Hi Heat Sink Temp
Activates the auxiliary output when the XW SCC heat sink
temperature rises above the trigger setting for the trigger delay time. Deactivates
the auxiliary output when the heat sink temperature falls below the clear setting
for the clear delay time. This setting can be used to trigger an alarm.
Fault
Activates the auxiliary output when a fault occurs. This setting can be
used to turn on an alarm or indicator light. When Fault is selected as the trigger
source, there is no programmable trigger level or clear level. You also cannot
select a specific fault as an auxiliary output trigger.
Trigger Source Configurable Ranges
This table contains the available configuration ranges and default settings for each
Trigger Source. The units, whether voltage or temperature, vary according to the
Trigger Source selected. If the selected Trigger Source is a Battery Voltage, the
range also varies according to the nominal battery voltage of your system.
Important:
Changing the Trigger Level resets the auxiliary output. If an auxiliary
output trigger is active, changing the trigger level will clear the trigger.
Table 3-6
Trigger Source Configuration Ranges
Trigger Source
Range
Default Trigger Default Clear
Low Batt Voltage
12V: 5–13V
24V: 10–26V
36V: 15–39V
48V: 20–52V
60V: 25–65V
11V
22V
33V
44V
55V
12V
24V
36V
48V
60V
Hi Batt Voltage
12V: 12–16V
24V: 24–32V
36V: 36–48V
48V: 48–64V
60V: 60–80V
14V
28V
42V
56V
70V
13V
26V
39V
52V
65V
Hi Array Voltage
10–145V
140V
130V
Hi Batt Temp
30.0–60.0 C
45.0 C
35.0 C
Low Batt Temp
-30.0–10.0 C
0.0 C
5.0 C
Hi Heat Sink Temp
50–95 C
75 C
70 C