Pre-Configuration Planning
976-0043-01-02
2–17
disconnect switches. A sample of this warning label is provided in
Figure
2-2
. These labels are not available or provided by Xantrex, but may be
available from your local electrical warehouse.
DC disconnects and
overcurrent devices
The size of the bonding jumper must be the same gauge as that of the
primary battery cable in which the overcurrent device (DC disconnect) is
installed, and as always, the overcurrent device must be sized
appropriately for all cables attached to it. If one overcurrent device trips
then there will be only half the amount of current available for both
inverters to run from. If you want to run only one inverter while the other
is shut down (for example, for maintenance procedures), the positive
bonding jumper must be removed or there must be an appropriately sized
switch installed in the bonding jumper.
Battery Temperature
Cold temperatures
Cold temperatures drastically reduce battery capacity and performance.
Therefore, the battery enclosure should provide a fairly stable temperature
for the batteries. If batteries are installed in a cold environment, insulation
should be installed to protect the batteries from the cold. The insulation
will act as a barrier to the cold and also keeps the heat generated by the
batteries inside the enclosure providing a more stable temperature and
better system performance.
Hot temperatures
High battery temperatures shorten the life of the batteries. The battery
enclosure should not be installed in direct sunlight where the sun can
overheat the batteries. Locate the enclosure where it will be protected
from the sun and provide vents in the top and bottom of the enclosure to
provide air flow throughout the enclosure.
For best performance, locate the batteries where they are in a room
temperature of 20 to 25 °C (68 to 77 °F)
Battery temperature
sensor
A Battery Temperature Sensor (BTS) is provided with each
Sine Wave
Plus
. This sensor can easily be installed in the system to ensure proper
charging of the batteries based on temperature. Installing a sensor extends
battery life by preventing overcharging in warm temperatures and
undercharging in cold temperatures.
Figure 2-2
Sample Warning Sticker for Backfeed Conditions
WARNING: Shock Hazard
Load side terminals may
be energized by
backfeed.
Not provided by Xantrex.
May be available at your local
electrical warehouse.
Содержание SW Plus 2524
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 02 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 02 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 02 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 141: ...Menu Map 976 0043 01 02 5 9 Figure 5 10 User Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 02 5 11 Figure 5 12 Basic Setup Menu Map Part 2...
Страница 145: ...Menu Map 976 0043 01 02 5 13 Figure 5 14 Advanced Setup Menu Map Part 2...
Страница 146: ...Navigation 5 14 976 0043 01 02 Figure 5 15 Complete User Menu Map...
Страница 147: ...Menu Map 976 0043 01 02 5 15 Figure 5 16 Complete Basic Setup Menu Map...
Страница 148: ...Navigation 5 16 976 0043 01 02 Figure 5 17 Complete Advanced Setup Menu Map...
Страница 200: ...Advanced Setup 7 22 976 0043 01 02 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 250: ...8 32...
Страница 274: ...A 16...
Страница 308: ...C 18...
Страница 312: ...D 4...
Страница 316: ...E 4...
Страница 338: ...I 6...
Страница 342: ...Index IX 4 976 0043 01 02...
Страница 343: ......