Connecting the AC Output Wires
To make the AC output wiring connections:
1.
Remove one of the AC knockouts from the front or side of the unit. Do
not leave the knockout inside the wiring compartment.
2.
Install a strain-relief clamp in the AC knockout and run the AC wiring
through the strain-relief clamp.
3.
Strip approximately 2 inches (50 mm) off the jacket from the AC cable
and separate the wires.
4.
Using a 1/4" blade slot screwdriver, loosen the terminal screws on the
AC output terminals. Do not remove the screws.
5.
Connect the line and neutral wires to the output terminals (labeled AC
Output on the terminal block, Figure 7 on page 27) as follows:
6.
Tighten the terminal screws. Leave some slack wire inside the wiring
box.
7.
Connect the ground wires to a free position on the ground bus, Figure
7 on page 27. If solid ground wire is being used, the wire can be
connected directly under the screw heads. If stranded ground wire is
being used, ring terminals must also be used.
8.
Secure the strain-relief clamp on the AC output cable jacket.
9.
Attach the wiring compartment cover panel and tighten the four
screws.
10. Connect the outgoing AC wires to an AC load panel equipped with
circuit breakers.
EQUIPMENT DAMAGE
Do not connect the output of the inverter to any incoming AC source.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
IMPORTANT:
The applicable installation code may not allow you to run
the AC input and AC output wiring through the same AC knockout.
Freedom SW 3012/3024
Terminals
Line for
Dual Output
Lines for
Single Output
N2
Neutral 2
Unused
L2
Line 2
Unused
N1
Neutral 1
Neutral
L1
Line 1
Line
Freedom SW 2012/2024
Terminals
Lines for Output
N
Neutral
L
Line
Freedom SW 3K2K InvChg Install Guide.book Page 29 Wednesday, October 12, 2011 4:40 PM