ProTechTPS Total Protection System
Woodward
65
Reset Input
This contact is used to clear/reset all local module trip and alarm events from the
trip and alarm latches.
If it is desired to use one module’s contact inputs to also “Reset” the other
modules trip and alarm latches, each module’s Boolean Input Manager logic
function can be configured to do so. Each module’s Boolean Input Manager
function can be configured to accept, only its local Reset contact input, or a
specific module’s Reset contact input, or all modules’ Reset contact inputs.
Note—The Reset button on the front of the module is a local module command
only and cannot be connected to nor affect the “ORed” Reset contact input logic
on other modules.
Speed-Fail-Override Input
This is used as part of the Start Logic “Speed Fail Trip” function. When this
function is enabled, closing the Speed-Fail-Override contact overrides the Speed
Fail Trip. This is a level sensitive trigger so the contact must remain closed to
prevent the Speed Fail Trip until speed is greater than the speed fail setpoint.
Refer to the Start Logic section below for additional details.
If it is desired to use one module’s contact inputs to also function as the “Speed
Fail Override Input” for the other modules, the module’s Boolean Input Manager
logic function can be configured to do so. Each module’s Boolean Input Manager
function can be configured to accept, only its local Speed-Fail-Override contact
input, or a specific module’s Speed-Fail-Override contact input, or all modules’
Speed-Fail-Override contact inputs.
Dedicated Discrete Inputs Specifications
Number of Channels
3, (Start, Reset, Speed Fail Override)
Input Thresholds
<= 8 Vdc = “OFF”
>= 16 Vdc = “ON”
Input Current
3 mA ±5% at 24 V (for externally power wiring, see,
Chapter 2)
Wetting Current Supply
24 V at 2 W available (see installation diagrams,
Chapter 2). This power supply is current limited.
Max Input Voltage
32 V (for externally power wiring, see, Chapter 2)
Isolation
500 Vac from output to chassis and output to all
other circuits
Table 3-4. Dedicated Discrete Input Specifications
Configurable Inputs
Each module has 10 configurable analog/discrete inputs. Each input can be
configured as Not Used, Analog Input, or Discrete Input. User defined names can
be associated with each input.
Discrete Input Configuration Example
When configured as a discrete Input, the channel accepts a 0 / 24 Vdc discrete
input. NOTE: <6 Vdc = FALSE, >12 Vdc = TRUE. The Boolean output associated
with the Discrete input can be used in the user configured software.
Содержание ProTech TPS
Страница 36: ...ProTechTPS Total Protection System Manual 26710V1 34 Woodward Figure 2 7 Inside View of ProTechTPS ...
Страница 37: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 35 Figure 2 8 ProTechTPS Control Wiring Diagram ...
Страница 62: ...ProTechTPS Total Protection System Manual 26710V1 60 Woodward Figure 3 8 Simplex Trip Block Assembly ...
Страница 63: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 61 Figure 3 9 Dual Redundant Trip Block Assembly ...
Страница 74: ...ProTechTPS Total Protection System Manual 26710V1 72 Woodward Figure 3 14 Start Logic Diagram ...
Страница 122: ...ProTechTPS Total Protection System Manual 26710V1 120 Woodward Advanced Menu ...
Страница 124: ...ProTechTPS Total Protection System Manual 26710V1 122 Woodward Declarations ...