Manual 26710V1
ProTechTPS Total Protection System
Woodward
15
Chapter 2.
Installation
Introduction
This chapter provides instructions on how to mount and connect the ProTechTPS
overspeed safety device into a system. Hardware dimensions, ratings, and
jumper configurations are given to allow a customer to mount, wire, and
configure the ProTechTPS package to a specific application.
Electrical ratings, wiring requirements, and options are provided to allow a
customer to fully install the ProTechTPS into a new or existing application.
Unpacking
Before opening the shipping packaging, inspect the shipping container for
damage and document any damage.
Be careful when opening & removing the shipping container. You may retain the
original shipping container for unit storage or return shipping for suggested
refurbishment. (See Asset Management chapter for storage details.)
Be careful when unpacking the ProTechTPS system from the shipping container.
The precautions called out in the Electrostatic Discharge Awareness section
should be followed during unpacking, handling, installation and operation during
maintenance.
Once removed from the shipping packaging, check the device for signs of
damage such as a bent or dented case and loose or broken parts. If damage is
found, notify the shipper immediately.
System Installation Procedure
1. Review system manual to gain a complete understanding of the
ProTechTPS system.
2. Create a site specific wiring diagram by referencing included wiring
diagrams & constraints then perform mechanical and electrical installation
following this chapter’s instructions.
3. Visual
inspection
a. Verify that all mounting hardware is tightened and that no wires are
pinched.
b. Verify that no wiring insulation is nicked or abraded.
c. Verify that all terminal blocks are installed and terminal screws are
tight. (Follow control wiring instructions for all terminal blocks.)
d. If used, verify that speed sensors have been correctly installed, and
have the correct clearance from the speed gear (adjust if necessary).
See manual 82510, Magnetic Pickups and Proximity Switches for
Electronic Governors.
4. Apply power to each module (one at a time), and verify that each module
boots up and its front panel screen displays turbine speed.
5. If no special programming logic is used skip to step 11.
6. If special programming logic is required install ProTechTPS programming
and configuration tool (PCT) from provided PCT Installation CD on to the
desired computer and create system application program.
Содержание ProTech TPS
Страница 36: ...ProTechTPS Total Protection System Manual 26710V1 34 Woodward Figure 2 7 Inside View of ProTechTPS ...
Страница 37: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 35 Figure 2 8 ProTechTPS Control Wiring Diagram ...
Страница 62: ...ProTechTPS Total Protection System Manual 26710V1 60 Woodward Figure 3 8 Simplex Trip Block Assembly ...
Страница 63: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 61 Figure 3 9 Dual Redundant Trip Block Assembly ...
Страница 74: ...ProTechTPS Total Protection System Manual 26710V1 72 Woodward Figure 3 14 Start Logic Diagram ...
Страница 122: ...ProTechTPS Total Protection System Manual 26710V1 120 Woodward Advanced Menu ...
Страница 124: ...ProTechTPS Total Protection System Manual 26710V1 122 Woodward Declarations ...