7. Once the system application program is complete connect an extension (i.e.
straight-through, not null-modem) RS-232 serial cable from the respective
computer to any module’s (A, B, C) service port, and download the program
into the module.
8. From the respective module’s front panel copy downloaded program to
other unit modules.
9. From each module’s front panel, verify that the correct program has been
installed in each module by comparing unit CRC codes.
10. From each module’s front panel, enter the configuration mode and verify
that each of the overspeed and over-acceleration settings are correct.
11. Enter the configuration mode and configure all settings to the specific
application’s requirements.
12. Perform a full system checkout by verifying all system trips, alarms, and test
routines function correctly before starting the machinery/system.
13. When ready, start the turbine/machinery following the equipment
manufacturer’s recommended starting procedure.
Enclosures
Module identification is always from left to right, with module A on
the left, module B in the center, and module C on the right. This
applies to either the bulkhead-mount versions with the front cover
open, or the panel-mount versions with the back cover removed.
Depending on the model purchased, the ProTechTPS has either a bulkhead-
mounted or a panel-mounted enclosure package.
The bulkhead-mounted enclosure models are designed to be mounted on a wall
or skid next to the turbine and are rated for IP56-based environments. With these
models, field wiring access is through gland plates located on the bottom of the
enclosure. Figures 2-1, 2-2, and 2-3 display the bulkhead mounted ProTechTPS
model’s physical layout and mounting pattern.
The ProTechTPS panel-mounted enclosure models are designed for installation
within a control room panel or cabinet, and by itself, it cannot be bulkhead
mounted. Once installed within an IP56 rated panel or cabinet, the ProTechTPS
panel-mounted models are rated for IP56-based environments. A gasket is
attached to the rear side of the package’s bezel to properly seal the ProTechTPS
control’s face-plate & around the mounting studs to a panel. With these models,
field wiring access is located on the ProTechTPS control’s back side, and a back
cover is included to protect wiring terminals after installation. Figures 2-4 and 2-5
display the Panel-Mount ProTechTPS model’s layout and mounting pattern.
Содержание ProTech TPS
Страница 36: ...ProTechTPS Total Protection System Manual 26710V1 34 Woodward Figure 2 7 Inside View of ProTechTPS ...
Страница 37: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 35 Figure 2 8 ProTechTPS Control Wiring Diagram ...
Страница 62: ...ProTechTPS Total Protection System Manual 26710V1 60 Woodward Figure 3 8 Simplex Trip Block Assembly ...
Страница 63: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 61 Figure 3 9 Dual Redundant Trip Block Assembly ...
Страница 74: ...ProTechTPS Total Protection System Manual 26710V1 72 Woodward Figure 3 14 Start Logic Diagram ...
Страница 122: ...ProTechTPS Total Protection System Manual 26710V1 120 Woodward Advanced Menu ...
Страница 124: ...ProTechTPS Total Protection System Manual 26710V1 122 Woodward Declarations ...