Manual 26710V1
ProTechTPS Total Protection System
Woodward
57
Figure 3-5. Example TMR Trip Block Assembly Interface
Independent Trip Relay Output Specifications
Number of Channels
2 (actuated simultaneously)
Output Type
SPST Solid-state, Normally Open
Current Rating
1 A
Voltage Rating
24 V (32 V max)
Isolation
500 Vac from output to chassis and output to
all other circuits
Signal Cable Length
Must be limited to 1000 ft / 305 m (low
capacitance
16 AWG / 1.3 mm² pair)
Table 3-1a. Independent Trip Relay Specifications