ProTechTPS Total Protection System
Manual 26710V1
94
Woodward
Table 4-6. Analog Read Addresses (Code 04)
Note:
The Last Trip time and date indication registers (3:1001 - 1007) are provided for
use as a way to time-stamp when a trip condition occurs. With this logic, when a
trip condition occurs the first sensed trip condition will be indicated by one of the
registers (1:0101 - 0137) changing to a true state. When one of those registers
change to a true state, then the Last Trip time and date indication registers
(3:1001 - 1007) will indicate the sensed date and time of the event. This
Date/Time will remain in locked in these registers until the next trip condition
occurs.
ADDRESS
DESCRIPTION
UNITS
RANGE
3:0001
Speed (after Speed Red Mgr, if used)
RPM
0 to 32500
3:0002
Acceleration (after Accel Red Mgr, if used)
RPM/s
-32500 to 32500
3:0003
Module A Speed
RPM
0 to 32500
3:0004
Module A Acceleration
RPM/s
-32500 to 32500
3:0005
Module B Speed
RPM
0 to 32500
3:0006
Module B Acceleration
RPM/s
-32500 to 32500
3:0007
Module C Speed
RPM
0 to 32500
3:0008
Module C Acceleration
RPM/s
-32500 to 32500
3:0009 Overspeed
Setpoint
(Local)
RPM
0 to 32500
3:0101 to 0110 Analog Inputs (Local) 1 to 10
User Units
-32768 to 32767
3:0201 to 0210 Module A Analog Inputs 1 to 10
User Units
-32768 to 32767
3:0301 to 0310 Module B Analog Inputs 1 to 10
User Units
-32768 to 32767
3:0401 to 0410 Module C Analog Inputs 1 to 10
User Units
-32768 to 32767
3:0501
Trip Cycle Time 1
ms
0 to 65535
3:0502
Trip Cycle Time 2
ms
0 to 65535
3:0601
Test Mode Time Remaining
s
0 to 65535
3:0701
Speed Fail Time Remaining
s
0 to 65535
3:0801
Timer 1 Seconds
s
0 to 65535
3:0802
Timer 1 Milliseconds
ms
0 to 999
3:0803
Timer 2 Seconds
s
0 to 65535
3:0804
Timer 2 Milliseconds
ms
0 to 999
3:0805
Timer 3 Seconds
s
0 to 65535
3:0806
Timer 3 Milliseconds
ms
0 to 999
3:0807
Timer 4 Seconds
s
0 to 65535
3:0808
Timer 4 Milliseconds
ms
0 to 999
3:0809
Timer 5 Seconds
s
0 to 65535
3:0810
Timer 5 Milliseconds
ms
0 to 999
3:0901
Temp Overspeed Setpoint
RPM
0 to 65535
3:0902
Simulated Speed RPM
RPM
0 to 65535
3:1001
Last Trip Month
Months
1 to 12
3:1002
Last Trip Day
Days
1 to 31
3:1003
Last Trip Year
Years
2000 to 2099
3:1004
Last Trip Hour
Hours
0 to 23
3:1005
Last Trip Minute
Minutes
0 to 59
3:1006
Last Trip Second
Sec
0 to 59
3:1007
Last Trip Millisecond
ms
0 to 999
3:1101
Unit Health Status
Enum
0 to 2
3:1201
Auto-Sequence Test Status
Enum
0 to 3
Содержание ProTech TPS
Страница 36: ...ProTechTPS Total Protection System Manual 26710V1 34 Woodward Figure 2 7 Inside View of ProTechTPS ...
Страница 37: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 35 Figure 2 8 ProTechTPS Control Wiring Diagram ...
Страница 62: ...ProTechTPS Total Protection System Manual 26710V1 60 Woodward Figure 3 8 Simplex Trip Block Assembly ...
Страница 63: ...Manual 26710V1 ProTechTPS Total Protection System Woodward 61 Figure 3 9 Dual Redundant Trip Block Assembly ...
Страница 74: ...ProTechTPS Total Protection System Manual 26710V1 72 Woodward Figure 3 14 Start Logic Diagram ...
Страница 122: ...ProTechTPS Total Protection System Manual 26710V1 120 Woodward Advanced Menu ...
Страница 124: ...ProTechTPS Total Protection System Manual 26710V1 122 Woodward Declarations ...