Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 99/165
Time-Overcurrent Monitoring (TOC)
NOTE
All percentage indications of the current are in relation to the generator rated current (Parameter 29).
Function:
The user may configure two steps for time-overcurrent monitoring. The threshold values and delays
can be configured so that the individual set points are independent of each other. Overcurrent level 1 disconnects
lower overcurrent levels that are present over longer periods of time. Overcurrent level 2 disconnects the more
destructive higher currents quickly to protect against short circuit conditions.
I >>
(I )
I >
(I )
t
2
t
1
t [s]
I [%]
1
2
Figure 6-1: Characteristic of the time-overcurrent monitoring
Parameter
135
Gen.overcurrent
monitoring ON
Time-overcurrent monitoring
ON/OFF
ON
................ Generator overcurrent monitoring is enabled. The subsequent screens
of this function are displayed.
OFF
.............. Generator overcurrent monitoring is not performed. The subsequent
screens of this function are not displayed.
Parameter
136
Gen.overcurr. 1
resp.value 000%
Time-overcurrent: limit 1
0 to 300 %
The value configured in this screen is a percentage of the configured generator
rated current. If this level is reached or exceeded for the configured delay time, the
unit issues an alarm and opens the GCB.
Tripping of class F3 alarm
Parameter
137
Gen.overcurr. 1
Delay 00.00s
Time-overcurrent: delay 1
0.02 to 99.98 s
The generator time-overcurrent monitoring threshold limit 1 must be exceeded,
without interruption, for the time period configured here before the configured re-
lay will be energized.