Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 53/165
Automatic Mode (Second Display Line: Measuring Values)
NOTE
The bottom line can be scrolled using the "Message
↓
" push button. It is also possible, to scroll
through any alarms that may be present using the "Message
↓
" push button.
----------------
xxxxxxxxxxxxxxxx
Display in automatic mode, second line: measuring values
The following measured values are displayed in the "
xxxxxxxxxx
" area shown to
the left:
Basic screen:
•
generator cosphi/power factor
•
actual generator real power
•
the unit operation currently being carried out (synchronization, etc.)
Subordinate screen:
Depending on the unit's equipment
•
mains voltage
•
mains current/power
•
mains cosphi/power factor
•
analog inputs
•
generator real power
•
generator re-active power (determined using phase L1 current; also if "three-
phase" power measurement was selected)
•
operating hours
•
time remaining to the next maintenance call
•
start counter
•
battery voltage (power supply)
•
number of subscribers participating in load sharing
•
maximum generator current (slave pointer)
•
the four alarm messages which occurred first
•
time/date
•
energy counter kWh and kvarh
These screens are displayed in succession by pressing the "Message
↓
" push button. When the last screen has
been reached, the basic screen is displayed. If alarms have occurred, the related message texts are displayed in
the sequence of their occurrence prior to the basic screen. If unit functions are active (e.g. synchronization of the
GCB), the basic screen is superimposed with the corresponding message (e.g. " synchronization"). Following the
termination of the unit function, the basic screen is displayed again.