External Set Point Value
Parameter
76
Power setpoint
external ON
P set point: external set point value
ON/OFF
ON
................ The real power set point 2 value may be specified via an external
signal. The subsequent screens of this function are displayed. This
setpoint is enabled when terminal 5 ("Setpoint 1
↔
2") is energized.
OFF
.............. If this function is configured to "OFF", the control unit utilizes set
point 1 only. The external set point value specification cannot be car-
ried out via the 0-20 mA input. The subsequent screens of this func-
tion are not displayed.
Parameter
77
Analog input
0-00mA
P set point: range
0 to 20 / 4 to 20 mA
A 0 to 20 mA or 4 to 20 mA analog input of the power factor controller is selected
here depending on the type of input used.
0
to 20 mA
... Minimum value of the setpoint is 0 mA; maximum value is 20 mA.
4
to 20 mA
... Minimum value of the setpoint is 4 mA; maximum value is 20 mA.
CAUTION
The interchange power set point (import/export power) can be scaled. When controlling interchange
power, it is vital to ensure that a constant power setting is not configured simultaneously with an Im-
port or Export power setting when scaling the external analog input.
External setpoint
0/4 mA
C
I
E
I
E
External setpoint
20 mA
C
I
E
E
I
Parameter
78
Ext.setpoint
0mA 0000kW
P set point: minimum value
C/E/I 0 to 16,000 kW
The minimum real power value is defined here (e.g. 0 kW).
Parameter
79
Ext.setpoint
20mA 0000kW
P set point: maximum value
C/E/I 0 to 16,000 kW
The maximum real power value is defined here (e.g. 100 kW).