Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 159/165
Option
Parameter
100/400V; 5 A
Setting range
Standard
setting
Customer settings
Lev
el
CONFIGURE OUTPUTS
Configure Outputs
YES/NO NO
Y N
Y N
Analg.out.130131
OFF / 0 to 20 / 4 to 20 mA
OFF
Analg.out.130131 parameter
0 to 23
01
Analg.out.130131 0%
0 to 9,990
0000
Analg.out.130131 100%
0 to 9,990
0200
Analg.out.132133
OFF / 0 to 20 / 4 to 20 mA
OFF
Analg.out.132133 parameter
0 to 23
01
Analg.out.132133 0%
0 to 9,990
0000
Analg.out.132133 100%
0 to 9,990
0200
Pulse output 1
+kWh / -kWh
Pulse output 1
logic
positive/negative negative
Active energy
Pulse/kWh
0.1 to 150.0
001.0
Pulse output 2
+kvarh / -kvarh
Pulse output 2
logic
positive/negative negative
Reactive energy Pulse/kvah
0.1 to 150.0
001.0
CONFIGURE DRIVE
Configure Drive
YES/NO YES
Y N
Y N
Automatic idle
Running
ON/OFF OFF
on off
on off
Download and
open GCB
ON/OFF ON
on off
on off
Monitoring on
at f gen >
15 to 70 Hz
15 Hz
Monitoring on
after
0 to 99 s
08 s
CONFIGURE COUNTER
Configure Counters
YES/NO NO
Y N
Y N
Service interval
ON/OFF ON
on off
on off
Service interval
in
0 to 9.999 h
0300 h
Op.hours counter
ON/OFF ON
on off
on off
Op.hours counter
set
0 to 65,000 h
00000 h
Start counter
ON/OFF ON
on off
on off
Start counter
set
0 to 32,000
00000
Display kWh +-
on?
Y/N YY
Display kvarh +-
on?
Y/N YY
Time
00:00 to 23:59
00:00
Year,month
00 to 99, 1 to 12
00,00
Day,weekday
01 to 31, 1 to 7
00,0