Operation Manual 37107F
MFR 3 - Multi Function Relay
Page 64/165
© Woodward
Basic Settings
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Failure to ensure correct configuration of parameters may lead to incorrect measurements and the con-
trol failing to respond properly!
Parameter
11
Configure
Measuring YES
Configure base settings
YES/NO
Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES
.............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor
→
", "Digit
↑
" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO
................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Parameter
12
Generator number
00
Generator number
1 to 4
For multiple generator applications that are coupled via a CAN bus, a unique num-
ber must be assigned to each generator for differentiation purposes. The generator
number 1 should be assigned if the control is used in a single unit application. The
generator number entered here corresponds to the generator number in the program
LeoPC (in files for multiple generators).
Generator and Mains Environmental
Rated Values of the Frequency
Parameter
13
Generator freq.
f set 00.0Hz
Generator set point frequency
40.0 to 70.0 Hz
The generator frequency set point is entered in this screen. This is required for the
frequency controller in isolated and no-load operation. In most cases, the values en-
tered into this screen will be 50 Hz or 60 Hz. It is possible to enterdifferent values.
Parameter
14
Rated system
frequency 00.0Hz
System rated frequency
50/60 Hz
The rated frequency of the system is entered in this screen. This parameter depends
on the three-phase system in the relevant country.