37. Technical information, air/flue gas
routing
If the gas condensing boiler is installed with a balanced flue routed over an external wall
(type C13x), the rated boiler output in heating mode must be reduced to below 11 kW
(for appropriate measures, see chapter "Limiting the maximum output").
It must be possible to inspect the entire cross-section of the flues. Therefore, install an
appropriate cleaning and/or inspection aperture inside the boiler room; agree suitable
arrangements with your local flue gas inspector.
Flue connections are created using couplings and gaskets. Always arrange couplings
against the direction of the condensate flow.
Install the balanced flue with a slope
of at least 3° towards the gas condensing boiler. Install spacer clamps to secure
the positioning (see installation examples).
Connection to the balanced flue
The calculated length of the balanced flue system or the flue is derived from the straight
pipe length and the length of any pipe bends.
Example for a 60/100 system
1)
:
Straight balanced flue pipe, length 1.5 m L = straight bend length
1 x 87° bend ≙ 1.5 m
L = 1.5 m + 1 x 1.5 m + 2 x 1.3 m
2 x 45° bends ≙ 2 x 1.3 m
L = 5.6 m
Calculating the
balanced flue length
Note:
To avoid reciprocal interference between air and flue gas pipes routed above
the roof, we recommend maintaining a minimum clearance of 2.5 m between
the pipes.
1)
Equivalent length of the system:
60/100
80/125
87° bend
1.5 m
3 m
45° bend
1.3 m
1.5 m
Minimum duct size for room sealed operation C93x
Assuming: In the installation room:
2x inspection bends, 1x 87° bend and
1.5 m horizontal with 87° support bend
C93x
Flue pipe DN 80
8
9
10
11
12
13
14
15
16
17
18
19
20
100
110
120
130
140
150
160
Square duct [mm]
Connecting pipe
DN 60/100
Connecting pipe
DN 80/125
Max. vertical length [m]
a
a
8
9
10
11
12
13
14
15
16
17
18
19
20
110
120
130
140
150
160
Connecting pipe
DN 60/100
Connecting pipe
DN 80/125
Round duct [mm]
Max. vertical length [m]
Flue pipe DN 80
Ø
Max. duct length in [m]
Duct cross-section in [mm]
Connecting pipe
DN 60/100
round
Connecting pipe
DN 60/100
square
Flue pipe DN 60