67
34. High efficiency pump function
description
Factory settings for pump speeds
Troubleshooting
Appliance
output
Heating mode
DHW
Standby
heating mode
maximum
minimum
14 kW
70 %
45 %
55 %
30 %
20 kW
70 %
45 %
75 %
30 %
24 kW
70 %
45 %
85 %
30 %
Problem
Remedy
Individual radiators do not warm up
properly.
Carry out hydraulic balancing, i.e.
reduce the flow rate of hotter radiators.
Increase the pump speed (HG16).
In the spring and autumn, the required
room temperature is not achieved.
Increase the set room temperature at
the controller, e.g. with set value setting
± 4.
The required room temperature is not
achieved when outside temperatures
are very low.
Select a steeper heating curve at
the controller, e.g. increase the flow
temperature at standard outside
temperatures.