24. Parameter description
System configuration 01
Direct heating circuit on the condensing
optional additional mixer circuits via mixer modules
(factory setting)
• Burner is enabled subject to demand from the direct
heating circuit or optionally connected mixer circuits
• Internal appliance pump is enabled as a heating circuit
pump
• Thermostatic boiler control
Set value is specified by the heating circuit or
mixer circuits
• Input E2: not assigned
dHk
System configuration 02
One or more mixer circuits via mixer modules
(no direct heating circuit on the condensing boiler)
• Burner starts subject to demand from the connected
circuits with mixer
• Internal appliance pump is enabled as a feed pump
• Thermostatic boiler control set value is specified by
mixer circuits
• Input E2: not assigned
MK1
MK2
M
M
System configuration 11
Plate heat exchanger for system separation
• Burner is enabled subject to demand from the
header temperature control
• Feed/heating circuit pump (ZHP) enabled as a feed
pump for header demand
• Header temperature control
• Input E2: Head
er sensor
• Parameter HG08 (TVmax): 90 °C
• DHW cylinder connection see parameter HG61
SAF
SAF
E2
Hydraulic
separation
Low loss
header
System configuration 11
Low loss header with header sensor
• Burner is enabled subject to demand from the header
temperature control
• Internal appliance pump is enabled as a feed pump
• Header temperature control
• Input E2: Header sensor
• Parameter HG08 (TVmax): 90 °C
• Parameter HG14 (Output A1): HKP
• DHW cylinder connection see parameter HG61
E2
SAF
dHk
A1