31. Checking the combustion parameters
If the actual CO
2
or O
2
values lie outside their respective ranges, proceed as follows
:
1. Check the ionisation electrode and supply line.
2. Check the electrode gaps.
3. Carry out a 100 % calibration after working on the ionisation electrode.
Þ
see description HG43 in chapter “Parameter description”
4. If the CO
2
or O
2
value remains outside the respective range, the flue gas values can be adjusted via parameter HG43.
Check the electrodes for wear and contamination.
Clean the electrodes with a small brush (not with a wire brush) or sandpaper.
Check the electrode gaps. If the gaps do not correspond to the drawing or the electrodes are damaged, replace the elec-
trodes and gaskets and align them.
Tighten the electrode fixing screws with a torque of 2.3 ±0.2 Nm.
Bild: Abstand Ionisationselektrode
Bild: Abstand Zündelektrode