33. Setting the flow limiter
The combi boiler is fitted with an adjustable flow
limiter (DHW draw-off rate).
The flow limiter is shipped with a flow rate set at the factory
to 8 l/min.
The flow rate can be changed via the green rotary selector
on the flow limiter.
The flow limiter can be adjusted between 5 and 13 l/min.
Procedure:
• Manually pull out the green rotary selector forwards.
• Increase flow rate Þ
rotate counter clockwise in
+
direction.
• Reduce flow rate Þ
rotate clockwise in
-
direction.
Check the selected flow rate on the display of the
AM display module or the BM-2 programming unit.
• Manually push in the green rotary selector to lock it.
Recommended draw-off rate
Appliance type
ΔT=40 K
ΔT=50 K
CGB-2K-20
8.6 l/min
6.8 l/min
CGB-2K-24
10 l/min
8 l/min
Fig: Flow rate limiter