INCOMING SIGNALS FROM THE DOOR CONTROLLER

Signal

Connector Pins

Contact type & normal state

Note

Opening control Ka

(coming from the Main Lift 

Controller)

Connector pins

5-15

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

When the Door Controller is 

installed on a Front & Rear entrance 

car, it is important that the opening 

and closing commands have no 

common contacts between the two 

doors.

Shielded, Grounded Wire Highly 

Recommended

Closing control Kc

(coming from the Main Lift 

Controller)

Connector pins

3-15

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

Forced closing control at  low speed 

Kb

Connector pins

15-22

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

The main lift controller may 

signal the forced closing when the 

photocell (or similar device) shall be 

made inoperative due to a failure, or 

after several door closing failures.

Re-opening control Kn

Connector pins

15-23

These connections require dry 

(voltage free) contacts (both logics 

available)

Fire-Fighting Contact Kff

Connector pins

15-39

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

Contact K2TB

Connector pins

15-41

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

This signal allows the door 

controller to recognize different 

door opening widths in the same 

lift installation.

Given this signal, the opening and 

closing operations are carried out 

referring to an alternative TB (door 

width recorded by an additional 

self-learning cycle).

Encoder signals

Connector RJ45 (A)

Factory prewired connector

Contact KEOD

Connector pins

15-40

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

This connection is to signal the use 

of the Sematic E.O.D. Emergency 

Opening Device to the Door 

controller 

Handset (Optional)

Connector RJ45 (B)

Auxliary contact Kaux

Connector pins

15-42

These connections require dry 

(voltage free) contacts (contact 

open when inactive)

Not yet implemented

Note

: Sematic Drive System

©

 controller may be used also with incoming signal from the Main Lift Controller with voltage range between 

6 and 24 Vdc.

To use this feature:

• 

Remove the shunt between 37-38 connector pins

• 

Connect the 38 connector pin at the 0V DC external incoming signal Power supply

Содержание sematic SDS Rel. 3

Страница 1: ...pyright WITTUR 2020 DC PWM SDS Drive Rel 3 version 01 03 005 No part of this publication may be reproduced or translated even in part without prior written permission from WITTUR Subject to change wit...

Страница 2: ......

Страница 3: ...ming Mode PROG 19 5 4 Verify the correct working of the controller SDS 19 5 5 RESET SPEED PROFILE PROCEDURE 19 5 6 Controller setting for SDS DC PWM 22 6 Functions available 24 6 1 Reversing 24 6 1 1...

Страница 4: ...M position control Default 00 28 6 16 Skate type Param Code 26 28 6 17 AUX Input Param Code 32 28 6 17 1 Disabled default 28 6 17 2 Partial Reopening 28 6 18 IM reversing motion signal type Param Code...

Страница 5: ...ting by means of the Handset 38 9 2 Activation of Motor type by means of the Handset 38 9 3 Activation of Closing Rotation by means of the Handset 38 9 4 Activation of the Car Door Locking Device sett...

Страница 6: ......

Страница 7: ...ll not be disclosed to anyone wi thout Sematic s written consent apart from authorized representatives employed by the user which commits itself to the confidentiality clause The Company that makes us...

Страница 8: ...TEMS Automatic lift doors Frame and frameless glass doors Enhanced car door operator solutions Complete cabins Car Frames Custom integrated packages Special lift doors cabins and car frames ELEVATOR S...

Страница 9: ...ial supply 2 Process control 3 Product control 4 Conformity tests according to Sematic specifications Furthermore Sematic guarantees the performance life of its products only if correctly stored indoo...

Страница 10: ...ons or by means of the Sematic handset an optional 8 digit keypad and display accessory which can be connected to the card by an RJ45 plug The handset 4 is a key pad that allows viewing and modificati...

Страница 11: ...celeration Closing cycle C1 Closing acceleration C2 Closing high speed C3 Closing deceleration Key Ka Door opening Kc Door closing La Open Limit Lc Close limit Closing cycle Active reversing system Op...

Страница 12: ...2020 Drive Instruction Manual 2 2 DEFAULT PROFILES PARAM CODE 33 This parameter allows to select one of the five default speed profiles 50 low performance 100 standard performance 150 high performanc...

Страница 13: ...PEED separately adjustable for opening and closing REVERSAL SENSITIVITY Variable only operational on door closing cycle Suitable for use on a circuit capable of delivering not more than 5000 Arms symm...

Страница 14: ...ction Manual 4 SIGNALS TO FROM THE DOOR CONTROLLER 4 1 SEMATIC DRIVE SYSTEM DC PWM CONNECTIONS Adjustable internal motor overload protection The Sematic door drive system estimates the motor temperatu...

Страница 15: ...Max 12 Min 30 7 Plug type Motor encoder Use Copper Conductors Only Not Required Not Required Not Required 9 Tightening screw Control circuit Use Copper Conductors Only Not Required Max 0 6 Nm Min 0 5N...

Страница 16: ...ons require dry voltage free contacts both logics available Fire Fighting Contact Kff Connector pins 15 39 These connections require dry voltage free contacts contact open when inactive Contact K2TB C...

Страница 17: ...ng 3A 250Vac 30Vdc Connector pins 2 4 contact normally open Auxliary autput signal AUX Connector pins 34 35 These connections provide dry voltage free contact contact normally open These contacts can...

Страница 18: ...pag 26 6 3 Main Lift Controller Test Param Code 01 a pag 26 6 12 Protective Device Logic Kn Param Code 21 a pag 29 NOTE This connection method does not provide for Door Controller interaction with Fir...

Страница 19: ...d PM 2 004921 EN 808 001 000 SDS rel 3 Edition 22 July 2020 Drive Instruction Manual 4 4 COMPLETE CONNECTION FROM DETECTOR MEMCO E SERIES TO THE DOOR CONTROLLER Alternatives of detector connection MEM...

Страница 20: ...Controller ca 3 sec switches to the manual mode MAN 5 2 MANUAL MODE MAN When the Door Controller is working in manual mode the MAN red led is on whereas the other two red leds are off All signals com...

Страница 21: ...Note Eventually replace the fuse 3 Connect only the power supply cable 4 Verify that after switching ON the controller by the key ON the controller disply will light after 5 seconds 5 Switch OFF the c...

Страница 22: ...On 07 03 Aux Output Relay 00 01 02 03 00 Off 01 Gong While opening 02 Space percentage 03 Alarm signal 08 50 Space Percentage Percentage of the available space to operate the AUX relay 00 99 00 99 00...

Страница 23: ...table pulse 36 00 Max power Op 00 01 00 Off 01 On 37 01 LA out with NO command 00 01 00 Off 01 On 38 25 LA Threshold 05 40 39 00 Soft Degradation OP 00 01 00 Off 01 On 42 01 Fset Autoregulation 00 01...

Страница 24: ...Mode 00 01 00 Clutch closed 01 Clutch open 26 To be set as for door configuration Clutch Type 00 01 02 00 Alu clutch standards STD 01 Expansion clutch EXP 02 Expansion clutch EXP B 99 To be set as for...

Страница 25: ...99 DEFAULT PROFILES 100 General Option Revers System choice External when moving External when moving External when moving External when moving MLC Test When moving When moving When moving When moving...

Страница 26: ...obstacle is present the door controller does not allow the door to close until a Kb forced closing is given from the main lift controller If the reversing system is external MOVING PARKING the Door Co...

Страница 27: ...choose to consider or not to consider a recorded fault the case that the door controller detects the signal failure both Ka and Kc when the Main Lift Controller Test is activated 00 Off function disab...

Страница 28: ...careful assessments and check of the standards required in the Country of installation At the end of the first closing cycle the main lift controller takes the car to the Fire Fighters access floor i...

Страница 29: ...nce of an obstacle and is used only one protective device input 15 23 terminals for photocells 30 31 32 33 terminals for direct connection of protective barriers the other input must be shorted For ex...

Страница 30: ...ed profile setting are optimized for the Sematic 2000 US Expansion skate type 00 STD Skate Aluminium skate 01 EXP Skate Use this setting when you have a single hole in the upper fixing plate left pict...

Страница 31: ...lete opening of a doors LA contact limit open doors 6 18 3 Monostable pulse IM inversion of movement is active only for a preset time of 0 5 sec After this time interval the output is disabled 6 19 KB...

Страница 32: ...m stops 06 Motor thermal protection Motor over heating with motors where internal PTC sensor is present Auto reset when normal operating conditions are restored 07 Motor jerk Interruption of the motor...

Страница 33: ...the system is re powered for instance after power supply interruption it performs a reset cycle i e it searches a closing limit at low speed not a self learning cycle 7 2 SELF LEARNING CYCLE WITH THE...

Страница 34: ...al mode To make this connection ask Sematic for the appropriate adapter cod B147AABX see picture 3 a 16 mm diameter hole is required in any chosen position within the Car walls Note when the handset i...

Страница 35: ...Edition 22 July 2020 Drive Instruction Manual 8 2 USER HANDSET MENUS AND SUBMENUS Access to advanced options with user PASSWORD PC99 is reachable just with SCH or SEM PASSWORD With SCH PASSWORD you c...

Страница 36: ...the option On the display the following options are viewed PC00 REVERS SYSTEM CHOICE PC34 IM SIGNAL TYPE PC42 FSET SELF TUNING PC09 REVERS FORCE SETTING REVERS OFFSET SETTINGS Using the keys and scrol...

Страница 37: ...celleration start 03 Accelleration C3 Accelleration 04 High speed C4 High speed 05 Offset deceleration C5 Offset deceleration 06 Deceleration C6 Deceleration 07 Low speed C7 Low speed 8 6 1 Option Par...

Страница 38: ...AUX RELAY OUT PC37 LA OUT WITH NO COMMAND PC38 LA THRESHOLD For each of the above listed parameter the parameter name is displayed at the top the current value is displayed at the bottom with the rel...

Страница 39: ...the OK key to confirm it The following options are available BACK press key F1 to restore the Main Menu MENU press key F3 to restore the Main Menu 8 6 8 Option Change Password This option allows the u...

Страница 40: ...eys and run through the DOOR OPERATO SETUP and choose the MOTOR option Press the OK key to confirm the choice For Sematic Drive System DC PWM cod B157AAEX01 controller the following motor list is disp...

Страница 41: ...K key to confirm it The display shows the confirmed option and restores the menu DOOR OPERATION SETUP The following options are available BACK Press key F1 to restore the menu DOOR CONFIGURATION MENU...

Страница 42: ...xpressed in days hours minutes the cycle total number which have been performed in this working time and the manufacture date The following options are available BACK Press key F1 to restore the menu...

Страница 43: ...n it on again and reconnect the handset The upload starts again from the beginning 12 DOOR OPERATOR MAINTENANCE At least once a year complete the following checks Clean the doors tracks bottom tracks...

Страница 44: ......

Страница 45: ...YOUR GLOBAL PARTNER FOR COMPONENTS MODULES AND SYSTEMS IN THE ELEVATOR INDUSTRY More information about Wittur Group available on line a WITTUR brand a WITTUR brand a WITTUR brand...

Отзывы: