32
WILO SE 06/2018
40026
(25)
Current value
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
R 31.000
40027
(26)
Active setpoint value
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1/day
1/month
0.1 psi
RW
R (dp-v)
R (dT-v)
31.000
40041
(40)
Pump 1 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40042
(41)
Pump 2 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40043
(42)
Pump 3 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40062
(61)
Switch box state
BITMAP
0: SBM
1: SSM
R
31.000
40139 -
40140
(138-139)
Error state
BITMAP32
0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communication
20: Net supply
21: Leakage
R
31.000
40141
(140)
Acknowledge
BOOL
W
31.000
40142
(141)
Alarm history index
UINT16
RW
31.000
40143
(142)
Alarm history error code
UINT16
0.1
R
31.000
Holding
register
Name
Data type
Scale
& unit
Elements
Access
Added
Содержание Control EC-Fire
Страница 7: ...Fig 9 Fig 10 Fig 11...
Страница 8: ...Fig 12 Fig 13 Fig 14...
Страница 9: ...Fig 15 Fig 16...
Страница 10: ......
Страница 13: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 3...
Страница 16: ...Deutsch 6 WILO SE 06 2018...
Страница 43: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 33...
Страница 45: ...English Installation and operating instructions Wilo Control EC Fire 35...
Страница 48: ...English 38 WILO SE 06 2018...
Страница 75: ...English Installation and operating instructions Wilo Control EC Fire 65...
Страница 77: ...Fran ais Notice de montage et de mise en service Wilo Control EC Fire 67...
Страница 80: ...Fran ais 70 WILO SE 06 2018...
Страница 109: ......
Страница 110: ......