English
52
WILO SE 06/2018
5.41
Pump kick for “Ext. Off” allowed
Values: off, on
Factory setting: on
5.42
Interval between pump kicks
Value range: 1 … 336 h
Factory setting: 24 h
5.43
Running time of pump on pump kick
Value range: 0 … 60 s
Factory setting: 5 s
5.45
Behaviour during sensor fault –
number of pumps to be switched on
Value range: 0 … 3*
Factory setting: 0
5.58
Collective run signal (SBM) function
Values: on, run
Factory setting: run
5.59
Collective fault signal (SSM) function
Values: fall, raise
Factory setting: raise
5.62
Dry run delay time
Value range: 0 … 300 s
Factory setting: 15 s
5.63
Reactivation delay time after dry run
Value range: 0 … 300 s
Factory setting: 10 s
Menu no. /
Description
Display
Содержание Control EC-Fire
Страница 7: ...Fig 9 Fig 10 Fig 11...
Страница 8: ...Fig 12 Fig 13 Fig 14...
Страница 9: ...Fig 15 Fig 16...
Страница 10: ......
Страница 13: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 3...
Страница 16: ...Deutsch 6 WILO SE 06 2018...
Страница 43: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 33...
Страница 45: ...English Installation and operating instructions Wilo Control EC Fire 35...
Страница 48: ...English 38 WILO SE 06 2018...
Страница 75: ...English Installation and operating instructions Wilo Control EC Fire 65...
Страница 77: ...Fran ais Notice de montage et de mise en service Wilo Control EC Fire 67...
Страница 80: ...Fran ais 70 WILO SE 06 2018...
Страница 109: ......
Страница 110: ......