English
Installation and operating instructions Wilo-Control EC-Fire
47
Menu no. /
Description
Display
Menu 1.00: Control parameters
1.01
Pressure setpoint
Value range: 0.1 … 16.0 bar*
Factory setting: 4.0 bar
1.04
Activation threshold of the pump
(in % from default value in 1.01)
Value range: 50 … 99 %
Factory setting: 90 %
1.05
Deactivation threshold of the pump
(in % from default value in 1.01)
Value range: 101 … 130 %
Factory setting: 115 %
1.06
Pump switch-off time delay
Value range: 10 … 300 s
Factory setting: 180 s
1.10
Activation delay, peak-load pump
Value range: 1 … 10 s
Factory setting: 1 s
Menu 2.00: Communication parameters (Modbus)
2.01
ModBus approval
Values: off, on
Factory setting: off
2.02
ModBus: Baud rate
Values: 9600; 19200; 38400; 76800
Factory setting: 19200
2.03
ModBus: Slave address
Value range: 1 … 254
Factory setting: 10
Содержание Control EC-Fire
Страница 7: ...Fig 9 Fig 10 Fig 11...
Страница 8: ...Fig 12 Fig 13 Fig 14...
Страница 9: ...Fig 15 Fig 16...
Страница 10: ......
Страница 13: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 3...
Страница 16: ...Deutsch 6 WILO SE 06 2018...
Страница 43: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 33...
Страница 45: ...English Installation and operating instructions Wilo Control EC Fire 35...
Страница 48: ...English 38 WILO SE 06 2018...
Страница 75: ...English Installation and operating instructions Wilo Control EC Fire 65...
Страница 77: ...Fran ais Notice de montage et de mise en service Wilo Control EC Fire 67...
Страница 80: ...Fran ais 70 WILO SE 06 2018...
Страница 109: ......
Страница 110: ......